BASIC INFO
						
					
					
	 P+F KFD2-STC4-Ex1.2O SMART Transmitter Power Supply 1-channel isolated barrier Analog input
	Features
	• 1-channel isolated barrier
	• 24 V DC supply (Power Rail)
	• Input 2-wire and 3-wire SMART transmitters and 2-wire
	SMART current sources
	• Signal splitter (1 input and 2 outputs)
	• Dual output 0/4 mA ... 20 mA
	• Terminal blocks with test sockets
	• Up to SIL 3 acc. to IEC 61508
	Function
	This isolated barrier is used for intrinsic safety applications.
	The device supplies 2-wire and 3-wire SMART transmitters in
	a hazardous area, and can also be used with 2-wire SMART
	current sources.
	It transfers the analog input signal to the safe area as two
	isolated current values.
	Digital signals may be superimposed on the input signal in the
	hazardous or safe area and are transferred bi-directionally.
	If the HART communication resistance in the loop is too low,
	the internal resistance of 250 ohm between terminals 8, 9
	and 11, 12 can be used.
	Test sockets for the connection of HART communicators are
	integrated into the terminals of the device.
	Application
	The device supports the following SMART protocols:
	• HART
	• BRAIN
	• Foxboro
	General specifications
	Signal type Analog input
	Functional safety related parameters
	Safety Integrity Level (SIL) SIL 3
	Supply
	Connection Power Rail or terminals 14+, 15-
	Rated voltage Ur 20 ... 35 V DC
	Ripple within the supply tolerance
	Power dissipation 1.8 W
	Power consumption 2.4 W
	Input
	Connection side field side
	Connection terminals 1+, 2-, 3 or 5-, 6+
	Input signal 0/4 ... 20 mA
	Open circuit voltage/short-circuit current terminals 1+, 3-: 22.7 V / 38 mA
	Voltage drop terminals 5, 6 : ≤ 2.4 V at 20 mA
	Input resistance terminals 2-, 3: ≤ 76 ohm
	terminals 1+, 3: ≤ 500 ohm (250 ohm load)
	Available voltage terminals 1+, 3: ≥ 16 V at 20 mA
	Output
	Connection side control side
	Connection terminals 7-, 8+,9; 10-, 11+,12
	Load 0 ... 550 ohm at 20 mA
	Output signal 0/4 ... 20 mA (overload > 25 mA)
	Ripple ≤ 50 µA rms
	Transfer characteristics
	Deviation at 20 °C (68 °F), 0/4 ... 20 mA
	≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
	Influence of ambient temperature 0.25 µA/K
	Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
	control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
	Settling time 200 µs
	Rise time/fall time 20 µs
	Galvanic isolation
	Output/power supply functional insulation, rated insulation voltage 50 V AC
	Output/Output functional insulation, rated insulation voltage 50 V AC
	Indicators/settings
	Display elements LED
	Labeling space for labeling at the front
	Directive conformity
	Electromagnetic compatibility
	Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
	Conformity
	Electromagnetic compatibility NE 21:2011
	Degree of protection IEC 60529:2001
	Protection against electrical shock UL 61010-1:2012
	Ambient conditions
	Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
	Mechanical specifications
	Degree of protection IP20
	Connection screw terminals
	Mass approx. 200 g
	Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2
	Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
	Data for application in connection
	with hazardous areas
	EU-Type Examination Certificate BAS 99 ATEX 7060 X
	Marking ¬ II (1)G [Ex ia Ga] IIC , ¬ II (1)D [Ex ia Da] IIIC , ¬ I (M1) [Ex ia Ma] I
	Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
	Supply
	Maximum safe voltage Um 250 V (Attention! The rated voltage can be lower.)
	Equipment terminals 1+, 3-
	Voltage Uo 25.4 V
	Current Io 86.8 mA
	Power Po 551 mW
	Order number:
	KCD2-STC-Ex1    
	KCD2-STC-Ex1.ES
	KFD2-CRG2-Ex1.D
	KFD2-HLC-Ex1.D
	KFD2-HLC-Ex1.D.2W
	KFD2-STC4-Ex1
	KFD2-STC4-Ex1.2O
	KFD2-STC4-Ex1.2O.H
	KFD2-STC4-Ex1.H
	KFD2-STC4-Ex2
	KFU8-CRG2-Ex1.D
	KCD2-STC-Ex1.2O
	KCD2-STC-Ex1.2O.ES
	KCD2-STC-Ex1.ES.SP
	KCD2-STC-Ex1.SP
	KFD2-STC3-Ex1
	KFD2-STC4-Ex1-Y1
	KFD2-STC4-Ex1.2O-Y1
	KFD2-STC4-Ex1.ES
	KFD2-STC4-Ex2-Y1
	KFD2-STC5-Ex1
	KFD2-STC5-Ex1.2O
	KFD2-STC5-Ex1.2O.H
	KFD2-STC5-Ex1.H
	KFD2-STC5-Ex2
	KFD2-STC5-Ex2
	KFD2-STC5-Ex2
	KFD2-STV4-Ex1.2O-1
	KFD2-STV4-Ex2-1
	KFD2-STV4-Ex2-2
	KFD2-STV5-Ex1-1
	KCD2-STC-Ex1.2O.DE
	KFD2-HLC-Ex1.D.4S
	KFD2-STV4-Ex1.2O-2
	KCD2-STC-Ex1.HC
	KCD2-STC-Ex1.HC.SP
	KFD2-STC4-Ex1
	KFD2-STC4-Ex1-Y1
	KFD2-STC4-Ex1.2O
	KFD2-STC4-Ex1.2O-Y1
	KFD2-STC4-Ex1.2O.H
	KFD2-STC4-Ex1.H
	KFD2-STV4-Ex1-1
	KFD2-STV4-Ex1-2
	KFD2-STV4-Ex1.2O-1
	KFD2-STV4-Ex2-1
	KFD2-STV4-Ex2-2
	KFD2-STV4-Ex1.2O-2
	KFD2-STC3-Ex1
	KCD2-STC-Ex1-Y1
	
	
	
	
		 
	
		 
	
		 
	
		 
		-----------------------------------
	
		Lily
	
		HONGKONG XIEYUAN TECH CO., LIMITED
	
		T: 86-027-85581877 F: 86-027-85309780 
	
		Mail:lily@whxyauto.com 
	
		Ad: 7-A16,Caishen Commercial Plaza,Hankou Railway Station,Wuhan, Hubei, China
	
		Web: www.hkxytech.com
	 
			 
		 
	 
							 
											